Initial verification according to DIN VDE 0100-600

Before an electrical installation goes into operation, it has to be tested. DIN VDE 0100-600 describes how: first inspect, then test, then measure – and document everything. For existing installations, DIN VDE 0105-100 applies analogously to periodic verification, known to many in Germany's residential and commercial sector as the E-Check.

The procedure in practice

  • Inspection – check the selection and installation of the equipment, protective measures, labelling, cable cross-sections and accessibility before voltage is applied.
  • Continuity of protective conductors – low-resistance measurement of protective and equipotential bonding conductors.
  • Insulation resistance – measurement with the test voltage appropriate to the nominal voltage.
  • Loop impedance and line impedance – proof that the disconnection conditions are met in the event of a fault.
  • RCD test – determine the tripping current and tripping time of the residual current devices.
  • Phase rotation and function – check the direction of phase rotation, test the protective devices.
  • Reporting – document the measured values, the assessment and the test equipment used.

Suitable test instruments

Testboy TV 456

Battery-powered installation tester

Test instrument for installation testing according to DIN VDE 0100 – for the complete scope of measurements in initial verification.

to the installation testers

Testboy TV 455

With test lead compensation

Further development of the proven TV 445, likewise for tests according to DIN VDE 0100-600, with a large LCD.

to the installation testers

TV 431 and TV 441

For individual measurements

The TV 431 insulation tester with four selectable test voltages and the TV 441 earth resistance tester are targeted additions to the installation tester.

to the category

This overview does not replace the text of the standard. Tests on electrical installations may only be carried out by a qualified electrician; the scope of testing and the assessment depend on the respective installation.